某地区新建2台1000MW超超临界火力发电机组,以500kV接入电网,每台机组设一组动力用220V蓄电池,均无端电池,采用单母线接线,两台机组的220V母...

作者: rantiku 人气: - 评论: 0
问题 某地区新建2台1000MW超超临界火力发电机组,以500kV接入电网,每台机组设一组动力用220V蓄电池,均无端电池,采用单母线接线,两台机组的220V母线之间设联络电器,单体电池的浮充电压为2.23V,均充电压为2.33V,该工程每台机组220V直流负荷如下表,电动机的启动电流倍数为2.
选项 220V蓄电池的个数应选择 (A)109个 (B)104个 (C)100个 (D)114个
答案 B
解析 依据DL/T5044-2004之附录B.1,蓄电池个数:n=1.05*220/2.23=104个均充电压Uc=1.125*220/104=2.37≥2.33,B满足

猜你喜欢

发表评论
更多 网友评论0 条评论)
暂无评论
错误啦!

错误信息

  • 消息: [程序异常] : MISCONF Redis is configured to save RDB snapshots, but it's currently unable to persist to disk. Commands that may modify the data set are disabled, because this instance is configured to report errors during writes if RDB snapshotting fails (stop-writes-on-bgsave-error option). Please check the Redis logs for details about the RDB error.