水电厂用低压断路器保护的回路,短路电流不应小于断路器瞬时或短延时过电流脱扣器整定电流的()。A.1.2倍;B.1.3倍;C.1.4倍;D.1.5倍。

作者: rantiku 人气: - 评论: 0
问题 水电厂用低压断路器保护的回路,短路电流不应小于断路器瞬时或短延时过电流脱扣器整定电流的()。
选项 A.1.2倍; B.1.3倍; C.1.4倍; D.1.5倍。
答案 B
解析

猜你喜欢

发表评论
更多 网友评论0 条评论)
暂无评论
错误啦!

错误信息

  • 消息: [程序异常] : MISCONF Redis is configured to save RDB snapshots, but it's currently unable to persist to disk. Commands that may modify the data set are disabled, because this instance is configured to report errors during writes if RDB snapshotting fails (stop-writes-on-bgsave-error option). Please check the Redis logs for details about the RDB error.